C01150 | l_phaseintk: function, C01151 | l_phaseintk: compare, C01201 | mck: cycle – Lenze 8400 HighLine User Manual

Page 1062: C01201/1, Hen the cycle, C1201/1, Is set to, 15 parameter reference

Advertising
background image

15

Parameter reference

15.2

Parameter list | C01150

1062

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C01150

C01151

C01201

Parameter | Name:

C01150 | L_PhaseIntK: Function

Data type: UNSIGNED_8

Index: 23425

d

= 5B81

h

Loading behaviour of the integrator
Selection list

Info

0 Loading with level

Load integrator with TRUE level at the input bLoad

1 Loading with edge

Load integrator with FALSE/TRUE edge at the input

bLoad

2 Loading with level + reset

Load integrator when the comparison value (

C01151

) is

reached or with TRUE level at the bLoad input

Subcodes

Lenze setting

Info

C01150/1

0: Loading with level

L_PhaseIntK_1

: Function

C01150/2

0: Loading with level

L_PhaseIntK_2

: Function

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01151 | L_PhaseIntK: Compare

Data type: INTEGER_32

Index: 23424

d

= 5B80

h

Comparison value
Setting range

(min. value | unit | max. value)

0

2147418112

Subcodes

Lenze setting

Info

C01151/1

0

L_PhaseIntK_1

: Comparison value

C01151/2

0

L_PhaseIntK_2

: Comparison value

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01201 | MCK: Cycle

Data type: INTEGER_32

Index: 23374

d

= 5B4E

h

From version 06.00.00

Cycle for Modulo measuring system

• When the cycle is set to 0 units (Lenze setting), the traversing range is unlimited (classical measuring system).

Activation of the Modulo measuring system

Setting range

(min. value | unit | max. value)

0.0000

units

214748.3647

Subcodes

Lenze setting

Info

C01201/1

0.0000 units

MCK: Cycle

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10000