Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

819

15

Parameter reference

15.2

Parameter list | C00079

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00079

C00080

C00081

Parameter | Name:

C00079 | SC: Settings

Data type: UNSIGNED_8

Index: 24496

d

= 5FB0

h

Configuration of different options for servo control (

SC

) and sensorless control for synchronous motors (

SLPSM

)

Selection list

0 Off
1 On

Subcodes

Lenze setting

Info

C00079/1

0: Off

SC

: Current controller - feedforward control

• Please observe the notes regarding this function in

the chapter "

Feedforward control of the current

controller

"!

C00079/2

1: On

SC

: Adapt. VP in the field weakening range

• Speed-dependent adaptive field weakening

controller.

C00079/3

0: Off

SC

: n-ctrl anti-wind-up

• "Anti-wind-up" effect of the speed controller in case

of an output voltage limitation in the field weakening

range.

C00079/4

1: On

Field weakening for synchronous motors

From version 11.00.00

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00080 | Override point of field weakening

Data type: INTEGER_16

Index: 24495

d

= 5FAF

h

Offset of the override point of field weakening

• In the V/f characteristic control mode (

VFCplus

), the stall protection function or the max. permissible current in

the field weakening range can be adapted.

Setting range

(min. value | unit | max. value)

Lenze setting

-500

Hz

500 0 Hz

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00081 | Rated motor power

Data type: UNSIGNED_16

Index: 24494

d

= 5FAE

h

This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor

catalogue, the suitable value can be entered automatically.

Note:

It is mandatory to give the rated motor power for the sensorless vector control (

SLVC

) and the servo control (

SC

).

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

kW

500.00 11.00 kW

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100