Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

433

7

Technology applications

7.4

TA "Table positioning"

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Possibility 2: Changing the profile position via parameter data (SDO)
The parameter data channel of a fieldbus can also be used to change the position in a profile.

• The position of the profiles 1 ... 15 are stored in the subcodes 1 ... 15 of the code

C01301

.

• More than 15 positions are available via the profile changeover (as described under possibility

1).

Possibility 3: Changing the profile position via process data (PDO)
For selecting the position in [increments], the dnPosProfilePosition_p input at the application block

is available.

The acceptance of the position into the currently selected profile is executed with a FALSE-TRUE

edge at the bPosSetProfilePosition input.

• If bit 2 is set in

C01297

, the applied setpoint position is accepted into the currently selected

profile and the profile is started directly when setting the process input bPosExecute to TRUE or

setting the control bit "PosExecute" in the

MCK control word

.

• If bit 3 is set in

C01297

, the setpoint positions at the MCKInterface are automatically accepted

into the profile with the applied profile number if a change of data is detected at the

corresponding input for the setpoint position.

• The accepted position is stored in the code

C01301/x

in the application unit [units]. By reading

out the code, you can check if the position was correctly accepted into the profile.

Note!

From version 04.00.00:

For selecting the position in [units], the two inputs wPosProfileUnitsLW and

wPosProfileUnitsHW at the application block are available.

• In the application level, the position in the FB

L_MckCtrlInterface

is converted from

[units] to [increments] again and output to dnPosSetOut_p. For this purpose, the

respective mode for position calculation must be selected in

C01296/1

.

• Since the conversion is not executed within one controller cycle, the data at the

dnPosSetOut_p output can be out-of-date. The bPosSetDataValid output is set to TRUE

when the conversion is completed and the position in increments is valid. Then, the

position can be transmitted to the profile (see the following section).

Note!

How to store changed profile parameters safely against mains failure in the memory

module: Set

C00002/11

= "1: On / Start".