C00821 | l_digitallogic_1: truth table, C00822 | l_digitallogic_2: function, C00821/1 – Lenze 8400 HighLine User Manual

Page 972: C00821, C00821/8, Is used, 15 parameter reference

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00821

972

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00821

C00822

Parameter | Name:

C00821 | L_DigitalLogic_1: Truth table

Data type: UNSIGNED_8

Index: 23754

d

= 5CCA

h

The

L_DigitalLogic_1

FB: Parameterisation of the truth table

Selection list

0 False
1 True

Subcodes

Lenze setting

Info

C00821/1

0: FALSE

L_DigitalLogic_1

: bIn3...bIn1=0 0 0

C00821/2

0: FALSE

L_DigitalLogic_1

: bIn3...bIn1=0 0 1

C00821/3

0: FALSE

L_DigitalLogic_1

: bIn3...bIn1=0 1 0

C00821/4

0: FALSE

L_DigitalLogic_1

: bIn3...bIn1=0 1 1

C00821/5

0: FALSE

L_DigitalLogic_1

: bIn3...bIn1=1 0 0

C00821/6

0: FALSE

L_DigitalLogic_1

: bIn3...bIn1=1 0 1

C00821/7

0: FALSE

L_DigitalLogic_1

: bIn3...bIn1=1 1 0

C00821/8

0: FALSE

L_DigitalLogic_1

: bIn3...bIn1=1 1 1

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00822 | L_DigitalLogic_2: Function

Data type: UNSIGNED_8

Index: 23753

d

= 5CC9

h

The

L_DigitalLogic_2

FB: Selection of the internal logic function

Selection list

(Lenze setting printed in bold)

Info

0 bOut = 0

Constant value "FALSE"

1 bOut = 1

Constant value "TRUE"

2 bOut = bIn1 AND ... bIn3

AND operation

3 bOut = bIn1 OR ... bIn3

OR operation

4 bOut = f (truth table)

The truth table parameterised in

C00823

is used.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1