Required parameter settings before the motor parameter identification is executed

• For an extended motor parameter identification, a motor control suitable for the motor has to

be set in

C00006

. When the identification starts, this setting determines whether an

asynchronous motor or a synchronous motor has to be identified.

Selecting the control mode

( 146)

• The motor parameters listed in the table below are excluded from automatic identification and

must therefore be adapted to the used motor before motor parameter identification is carried

out (see motor nameplate).

• If the motor nameplate data are entered in the »Engineer« motor catalogue instead of selecting

a motor, it is recommendable to use the extended motor parameter identification

(

C02867/1

= "2: extended identification").

• Especially for third-party motors, it is also recommendable to carry out the slip calculation with

the motor equivalent circuit diagram data (

C02879/1

). If the slip calculation is derived from the

motor nameplate data, this can negatively affect the stability and accuracy of the drive

behaviour because the rated speed specified on the motor nameplate often is rather inaccurate.

• The available motor cable must be specified in terms of length and cross-section:

The motor cable resistance resulting from these settings is displayed in

C00917

.

• For the measurement of the required variables, the motor is energised via the controller

terminals U, V and W during the motor parameter identification. The corresponding current

controller is preset in the Lenze setting so that a optimal controller behaviour is achieved with

an asynchronous motor power-adapted to the controller.
Thanks to optimisation, the current controller can be set via the following parameters:

Parameter

Info

C00081

Rated motor power

C00087

Rated motor speed

C00088

Rated motor current (according to the connection method /)
NoteThe amplitude of the rated motor current (

C00088

) is injected to identify the stator

resistance. If the rated motor current amounts to less than 60 % of the rated inverter current,

at least 60 % of the rated inverter current will be injected to ensure sufficient motor

parameter identification accuracy.

C00089

Rated motor frequency (according to the connection method /)

C00090

Rated motor voltage (according to the connection method /)

C00091

Motor cos ϕ

Parameter

Info

C00915

Motor cable length

C00916

Motor cable cross-section

Parameter

Info

Lenze setting

Value Unit

C00075

Vp current controller

7.00 V/A

C00076

Ti current controller

10.61 ms