1305

17

Function library

17.1

Function blocks

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

17.1.53

L_ConvW_3

This FB serves to convert analog signal forms. The following conversions per parameter can be

selected:

• [%]  [incr/ms]
• [incr/ms]  [%]
• Conversion via parameterisable factors
• Input signal is passed through without conversion

Inputs

Outputs

Parameter

Identifier

Data type

Information/possible settings

wIn

WORD

Input signal

Identifier

Data type

Value/meaning

wOut

WORD

Output signal

Parameter

Possible settings

Info

C00940/3

-32767

32767 Numerator

• Lenze setting: 1

C00941/3

-32767

32767 Denominator

• Lenze setting: 1

C00942/3

Selection of the conversion

0 wOut = wIn (no conversion)
1 [%]  [incr/ms]
2 [incr/ms]  [%]
3 wOut = wIn *

C00940

/

C00941

For conversion formulae see

L_ConvW_1

.

/B&RQY:B

Z2XW

Z,Q

'HQRPLQDWRU
&RQYHUVLRQ

&
&
&

1XPHUDWRU