Field feedforward control
To have enough voltage reserve available for dynamic acceleration processes, a timely weakening

of the field is required. The field weakening is controlled by the field feedforward control.

The field feedforward control reciprocally reduces the magnetising current from the V/f base

frequency (

C00015

) on. The starting point of the reduction can be shifted to low frequencies via the

field feedforward control (

C00576

). Thus, more voltage reserve is available for acceleration

processes.
The field feedforward control (

C00576

) must be specified in %, based on the rated slip of the

machine.

Tip!
Generally, the Lenze setting is sufficient for most applications.

• We recommend to increase the field feedforward control for applications with very

dynamic acceleration processes in the field weakening range.

• Reduce the field feedforward control for very slow applications if necessary.

Parameter

Info

Lenze setting

Value Unit

C00576

SC: Field feedforward control

200.0 %

Note!

The function of the field feedforward control and thus the field weakening control

requires a correct setting of the V/f base frequency (

C00015

).

• The selection of the motor from the »Engineer« motor catalogue and the motor

parameter identification serve to set the V/f base frequency correctly.

• When third-party motors are entered, either the V/f base frequency (

C00015

) has to

be calculated manually or a motor parameter identification has to be carried out.

Adapting the V/f base frequency

( 161)

Automatic motor data identification

( 138)

Due to an error in the device software, the field feedforward control of the servo control

only operates properly if the V/f base frequency (

C00015

) is reduced by the following

factor after being set:

• 400-V devices: Factor 0.173
• 230-V devices: Factor 0.34

The same factor has to be considered for the field feedforward control (

C00576

).

From version 14.00.00

, the control parts can be called for an optimum jerk-free

transition to the field weakening range in a 500-

μ

s cycle. For this purpose, bit 5 has to be

set to "1" int in

C02864/1

.

• With this setting,

C00015

and

C00576

do not have any influence anymore on the field

feedforward control.

• We recommend this setting for new applications.