L_MFail inputs

Function

nAdapt_a

Dynamic adaptation of the proportional gain of the DC-bus voltage controller.

• Input not interconnected  Adaptation = 0 %.

nConst_a

Proportional gain of the DC-bus voltage controller

• Input with nPos100_a constant interconnected  proportional gain = 100 %.

nDCSet_a

Voltage setpoint on which the DC-bus voltage is to be kept.

• The voltage setpoint has to be set in the "free parameter"

C00476/2

.

nNset_a

Speed setpoint path (output: nNOut_a)

bFault

Activating the mains failure control

Procedure of the mains failure control ( 1397)

bReset

Reset mains failure control

• The free bFreeIn2 input of the application block used in the example can be e.g.

connected to a digital input on I/O level.

nThreshold_a

Restart threshold

• The restart threshold (at first approx 2 %) has to be set in the "free parameter"

C00476/3

.

nNAct_a

Comparison value for the restart threshold

• Comparison value is the actual speed value

nSet_a

Speed starting point for the deceleration

• Speed starting point is the actual speed value

nDCVoltAct_a

Actual DC-bus voltage