Basic settings

538

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Operating mode
If the limit for the following error in

C01215/x

is set higher than "0.0000 units" and if the current

following error exceeds this limit over the time set in

C01244/x

:

• The error response set in

C00595/5

or

C00595/6

will be carried out (Lenze setting: "Warning").

• The error message "

Ck05: Error, following error 1

" or "

Ck06: Error, following error 2

" will be

entered into the logbook.

• The status output bFollowErrLim1 or bFollowErrLim2 at the SB

LS_MotionControlKernel

is set to

TRUE.

8.4.6.1

Monitoring of the following error in case of controller inhibit

Up to and including version 13.xx.xx

, the setpoint position is always set = actual position in case of

controller inhibit.

From version 14.00.00

onwards, the setpoint position is only set = actual position if the current

following error reaches the limit value set in

C01215/3

.

• In the Lenze setting

C01215/3

= "0.0000 units" the behaviour is as before, i.e. the setpoint

position is immediately set = actual position in case of controller inhibit.

Application example
In case ofa continuous relative positioning by 100 units and a setting of the controller inhibit after

each positioning process (e.g. by means of the

Holding brake control

in the "automatically

controlled" mode), it is expected that after 10 positioning processes, an absolute target of

10 x 100 units = 1000 units has been reached.
Without setting a limit value (

C01215/3

=0), the continuous setting of the setpoint position to the

actual position in case of controller inhibit causes a drifting of the setpoint position due to the

drifting of the actual position at standstill. After ten positioning processes, only e.g. 999.5 units have

been reached instead of 1000 units. If, however, the setpoint position is not set to the actual

position (

C01215/3

<> 0) in case of controller inhibit, the setpoint position is exactly in the target

after 10 positioning processes and 9 x controller inhibits (in case of 10 x relative traverse paths).

Parameter

Info

Lenze setting

Value Unit

C01215/3

MCK: Following error SetPos=ActPos

0.0000 units

Note!

The limit value set in

C01215/3

should not be set higher than the drift of the actual

position at standstill of the drive plus a possible safety option. Otherwise, the position

controller carries out an intermittent compensation after the controller inhibit is

deactivated due to the pending system deviation!