3 motor overcurrent monitoring, Motor overcurrent monitoring, 5motor control (mctrl) – Lenze 8400 HighLine User Manual

Page 298

Advertising
background image

5

Motor control (MCTRL)

5.14

Monitoring

298

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Tip!

• If forced ventilated motors are used, a premature response of the overload threshold can

be avoided by deactivating this function if necessary (

C00606

= "0: No Reaction").

• The current limits set in

C00022

and

C00023

influence the I

2

xt calculation only in an

indirect way. However, the operation of the motor at maximum possible load can be

averted.

Defining current and speed limits

( 151)

5.14.3

Motor overcurrent monitoring

The ultimate motor current to be parameterised in

C00939

is a limit value to protect the motor from

destruction, influence of the rated data and demagnetisation.

• This limit value must not be travelled cyclically in the drive process.
• If the instantaneous value of the motor current exceeds the limit value set in

C00939

, the error

response "Fault" occurs to protect the motor and the error message "

oC7: Motor overcurrent

" is

entered into the logbook.

• The maximum currents to be parameterised in

C00022

and

C00023

should have a sufficient

distance to this limit value.

Related topics:

Maximum current monitoring

( 305)

Note!

If a Lenze motor is selected from the catalogue whose plant parameters are transferred

into the controller, the setting of the maximum current in

C00022

and

C00023

will

automatically be adapted to the selected motor.