C00560 | fan switching status, C00561 | failure indication, C00565 | resp. to mains phase failure – Lenze 8400 HighLine User Manual

Page 914: C00565, E logbook and, C00561/3, Stil, Motor phas, C00561/4, C00561/5

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00560

914

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00560

C00561

C00565

Parameter | Name:

C00560 | Fan switching status

Data type: UNSIGNED_8

Index: 24015

d

= 5DCF

h

Display of the function status of the device fans
Selection list

0 Off
1 On
2 No fan

Subcodes

Info

C00560/1

Switching status - internal fan

C00560/2

Switching status - heatsink fan

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00561 | Failure indication

Data type: UNSIGNED_8

Index: 24014

d

= 5DCE

h

Failure display of device fans and motor phases
Selection list

0 No error
1 Fault

Subcodes

Info

C00561/1

Internal fan

C00561/2

Heatsink fan

C00561/3

Motor phase U

From version 11.00.00

C00561/4

Motor phase V

From version 11.00.00

C00561/5

Motor phase W

From version 11.00.00

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00565 | Resp. to mains phase failure

Data type: UNSIGNED_8

Index: 24010

d

= 5DCA

h

Response to the failure of mains phases
Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
5 Warning

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Advertising