4 pdo synchronisation via sync telegram, Pdo synchronisation via sync telegram, 11 system bus "can on board – Lenze 8400 HighLine User Manual

Page 720

Advertising
background image

11

System bus "CAN on board"

11.8

Process data transfer

720

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11.8.4

PDO synchronisation via sync telegram

During cyclic transmission, one or more PDOs are transmitted/received in fixed time intervals. An

additional specific telegram, the so-called sync telegram, is used for synchronising cyclic process

data.

• The sync telegram is the trigger point for the transmission of process data from the slaves to the

master and for the acceptance of process data from the master in the slaves.

• For sync-controlled process data processing, the sync telegram must be generated accordingly.
• The response to a sync telegram is determined by the selected transmission

type.

Transmission type

( 718)

Basic workflow

[11-6] Sync telegram

A. After the sync telegram has been received, the slaves transmit the synchronous process data to

the master (TPDOs). The master reads them as process input data.

B. When the transmission process is completed, the slaves receive (RPDOs) the process output

data (of the master).

• All other telegrams (e.g. parameters or event-controlled process data) are accepted acyclically

by the slaves after the transmission is completed.

• Illustration

[11-6]

does not include acyclic data. However, they need to be considered when

dimensioning the cycle time.

C. The data are accepted in the slave with the next sync telegram if the Rx mode is set to 1 ... 240.

If the Rx mode is 254 or 255, the data are accepted in the next device cycle, irrespective of the

sync telegram.

Short overview: Parameters for the synchronisation via sync telegram

Related topics:

Synchronisation of the internal time base

( 774)

Sync cycle time (

C01121

)

Œ

SYNC

SYNC

0

1

2

Parameter

Info

Lenze setting

Assignment

Value Unit

Sync

master

Sync

slave

C00367

CAN SYNC Rx identifier

0x0080

C00368

CAN SYNC Tx identifier

0x0080

C00369

CAN sync transmission cycle time

0 ms

Advertising