15.2

Parameter list | C00006

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7 VFCplus: V/f linear + encoder

This control type is used for speed control of an

asynchronous motor via a linear V/f characteristic.

• The control type requires a speed feedback via an

encoder mounted to the motor!

• For setting the V/f characteristic, only the rated

frequency (

C00089

) and the rated voltage (

C00090

) of

the motor have to be entered.

V/f control

8 VFCplus: V/f quadr

This control type is used for speed control of an

asynchronous motor via a square-law V/f characteristic.

• For setting the V/f characteristic, only the rated

frequency (

C00089

) and the rated voltage (

C00090

) of

the motor have to be entered.

V/f characteristic control

9 VFCplus: V/f quadr + encoder

This control type is used for speed control of an

asynchronous motor via a square-law V/f characteristic.

• The control type requires a speed feedback via an

encoder mounted to the motor!

• For setting the V/f characteristic, only the rated

frequency (

C00089

) and the rated voltage (

C00090

) of

the motor have to be entered.

V/f control

10 VFCplus: V/f definable

From version 04.00.00

This type of control is used for the speed control of an

asynchronous motor via a user-definable characteristic

with several interpolation points.

• For setting the V/f characteristic, only the rated

frequency (

C00089

) and the rated voltage (

C00090

) of

the motor have to be entered.

V/f characteristic control

11 VFCplusEco: V/f energy-saving

From version 10.00.00

This control type is used for energy-saving speed control

of an asynchronous motor via a linear V/f characteristic.

• For setting the V/f characteristic, only the rated

frequency (

C00089

) and the rated voltage (

C00090

) of

the motor have to be entered.

• Predestinated application areas of this control type

are materials handling technology and pump and fan

systems.

V/f characteristic control, energy-saving