63

3

Commissioning

3.7

Commissioning of the "Actuating drive speed" technology application

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.7.5

Saving parameter settings safe against mains failure

The parameter set must be saved to the device safe against mains failure to prevent parameter

settings becoming lost due to mains switching.

Save parameter set.

3.7.6

Enable controller and test application

If the controller is in the "

SwitchedOn

" status:

1. Enable controller: Set terminal X5/RFR to HIGH level or close contact.

• If there is no other active source for the controller inhibit, the controller changes from the

"

SwitchedOn

" status to the "

OperationEnabled

" status.

• The Diagnostics tab and

C00158

display all active sources for the controller inhibit.

2. Select the speed setpoint.

In the "Terminal 0" control mode by selecting a voltage at the analog input via the setpoint

potentiometer or by selecting a fixed setpoint via the digital DI1/DI2 inputs:

Stop!

Before stipulating a speed setpoint, check whether the brake in the form of a holding

brake on the motor shaft has been released!

Note!

If the controller is enabled and the "Inhibit at power-on" auto-start option is activated in

C00142

(Lenze setting) when the mains is connected, the controller remains in the

"

ReadyToSwitchOn

" state.

To be able to change to the "

SwitchedOn

" status, the controller enable must be

deactivated first: set terminal X5/RFR to LOW level.

DI1

DI2

Speed selection

LOW

LOW

The setpoint speed is selected via analog input 1

• Scaling: 10 V ≡ 100 % ≡ reference speed (

C00011

)

HIGH

LOW

Fixed setpoint 1 (

C00039/1

) is used as setpoint speed.

• Lenze setting: 40 % of the reference speed (

C00011

)

LOW

HIGH

Fixed setpoint 2 (

C00039/2

) is used as setpoint speed.

• Lenze setting: 60 % of the reference speed (

C00011

)

HIGH

HIGH

Fixed setpoint 3 (

C00039/3

) is used as setpoint speed.

• Lenze setting: 80 % of the reference speed (

C00011

)

Note!

Observe the actual speed value (display in

C00051

) as well as the

LED status displays

.

( 616)