C00634 | l_nset_1: wstate, C00635 | l_nset_1: nmaxlimit, C00636 | l_nset_1: nminlimit – Lenze 8400 HighLine User Manual

Page 940: C00635, C00636, 15 parameter reference

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00634

940

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00634

C00635

C00636

Parameter | Name:

C00634 | L_NSet_1: wState

Data type: UNSIGNED_16

Index: 23941

d

= 5D85

h

The

L_NSet_1

FB: Bit coded status display

Display area

(min. hex value | max. hex value)

0x0000

0xFFFF

Value is bit-coded:

Info

Bit 0 No blocking zone active

1 ≡ No blocking zone set for constant speeds

Bit 1 Blocking zone 1 active

1 ≡ Suppression of constant speed characteristics within

the limits of blocking zone 1

Bit 2 Blocking zone 2 active

1 ≡ Suppression of constant speed characteristics within

the limits of blocking zone 2

Bit 3 Blocking zone 3 active

1 ≡ Suppression of constant speed characteristics within

the limits of blocking zone 3

Bit 4 Jog in blocking zone

1 ≡ A ramp is used to keep the speed setpoint within a

speed blocking zone

Bit 5 MaxLimit active

1 ≡ Speed setpoint is at the maximum speed limit

Bit 6 MinLimit active

1 ≡ Speed setpoint is at the minimum speed limit

Bit 7

Reserved

Bit 8

Reserved

Bit 9

Reserved

Bit 10

Reserved

Bit 11

Reserved

Bit 12

Reserved

Bit 13

Reserved

Bit 14

Reserved

Bit 15

Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C00635 | L_NSet_1: nMaxLimit

Data type: INTEGER_16

Index: 23940

d

= 5D84

h

The

L_NSet_1

FB: Maximum speed setpoint for speed setpoint limitation

Setting range

(min. value | unit | max. value)

Lenze setting

-199.99

%

199.99 199.99 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00636 | L_NSet_1: nMinLimit

Data type: INTEGER_16

Index: 23939

d

= 5D83

h

The

L_NSet_1

FB: Minimum speed setpoint for speed setpoint limitation

Setting range

(min. value | unit | max. value)

Lenze setting

-199.99

%

199.99 -199.99 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100