Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

331

6

I/O terminals

6.1

Digital input terminals

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Counting behaviour
The following temporal characteristic shows the counting process depending on the signals of the

interfaces described before:

[6-1]

Transient characteristic of a quick counter block, sampling cycle = 1 ms

• The counter starts with the parameterised starting value.
• If the comparison value is reached or exceeded:

• The counter jumps back to its starting value.
• The output bCount1(6)_Compare is set to TRUE.

• If there is a FALSE-TRUE edge is at the input bCountIn1(6)_ResetCompare, the output

bCountIn1(6)_Compare can be reset to FALSE.

• If there is a FALSE-TRUE edge at the input bCountIn1(6)_LoadStartValue, the current counter

content can be reset to the parameterised starting value.

Related topics:

Using DI1(6) and DI2(7) as digital inputs

( 322)

Using DI1(6) and DI2(7) as frequency inputs

( 323)

Internal interfaces | System block "LS_DigitalInput"

( 332)

E&RXQW,QB5HVHW&RPSDUH

W

E&RXQW,QB/RDG6WDUW9DOXH

W

E&RXQW,QB&RPSDUH

W

W

&

&




























































&

&RXQWSXOVH

6DPSOLQJF\FOH

&RXQWHUYDOXH

6WDUWYDOXH

&RPSDUHYDOXH