Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.14.10

Maximum torque monitoring

This function extension is only available from version 04.00.00!

If the maximum possible torque

C00057

is reached at the motor shaft, the response set in

C00608

will be carried out (Lenze setting: "0: No Reaction").
If the activated monitoring is tripped:

• The "

oT1: Maximum torque reached

" error message is entered into the logbook.

• The bMctrlTorqueMax status output of the

LS_DeviceMonitor

system block will be set to TRUE.

5.14.11

Motor speed monitoring

This function extension is available from version 11.00.00!

If the drive reaches the maximally permissible motor speed (

C00965

):

• The error response "Fault" occurs, i.e. the inverter is inhibited and the motor changes to torque-

free operation (coasts down).

• The error message "

oS2: Max. motor speed reached

" is entered into the logbook.

Note!

In the Lenze setting (

C00608

= "0: No Reaction"), the maximum torque monitoring is not

activated!