Xx.0131.00015, Xx.0135.00001, Xx.0135.00002 – Lenze 8400 HighLine User Manual

Page 658: Xx.0135.00003, Xx.0135.00004, 9diagnostics & error management

Advertising
background image

9

Diagnostics & error management

9.9

Error messages of the operating system

658

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CA0F: CAN control word [xx.0131.00015]

CE1: CAN RPDO1 [xx.0135.00001]

CE2: CAN RPDO2 [xx.0135.00002]

CE3: CAN RPDO3 [xx.0135.00003]

CE5: CAN RPDO4 [xx.0135.00004]

Response (Lenze setting printed in bold)

Setting:

C00594/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Bit 14 ("SetFail") in the wCANControl control word of the

LS_DriveInterface

system block has been set.

Trace back signal source on the CAN bus that sets bit 14

("SetFail").

Response (Lenze setting printed in bold)

Setting:

C00593/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: Time monitoring for RPDO1 has been

triggered.

• RPDO1 has not been received within the monitoring

time set in

C00357/1

or was faulty.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate electrical interference (e.g. EMC).

• Adjust monitoring time

C00357/1

or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C00593/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: Time monitoring for RPDO2 has been

triggered.

• RPDO2 has not been received within the monitoring

time set in

C00357/2

or was faulty.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate electrical interference (e.g. EMC).

• Adjust monitoring time

C00357/2

or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C00593/3

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: Time monitoring for RPDO3 has been

triggered.

• RPDO3 has not been received within the monitoring

time set in

C00357/3

or was faulty.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate electrical interference (e.g. EMC).

• Adjust monitoring time

C00357/3

or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C00593/4

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: Time monitoring for RPDO4 has been

triggered.

• RPDO4 has not been received within the monitoring

time set in

C00357/4

or was faulty.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate electrical interference (e.g. EMC).

• Adjust monitoring time

C00357/4

or switch off time

monitoring.

Advertising