Parameter list | C00029

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00029

C00033

C00034

Parameter | Name:

C00029 | AINx: Input current

Data type: INTEGER_16

Index: 24546

d

= 5FE2

h

Display of the input current at the analog inputs

• When the corresponding analog input is configured for current measurement (

C00034/x

= 1 or 2).

• When

C00034/x

is set = 2 (4 ... 20 mA), 0 ... 16 mA is displayed.

Analog terminals

Display range

(min. value | unit | max. value)

0.00

mA

20.00

Subcodes

Info

C00029/1

AIN1: Input current

C00029/2

AIN2: Input current

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00033 | AINx: Output value

Data type: INTEGER_16

Index: 24542

d

= 5FDE

h

Display of the output value in percent of the analog input amplifier

• 100 % ≡ 16384 ≡ +10 V / +20 mA

Analog terminals

Display range

(min. value | unit | max. value)

-199.99

%

199.99

Subcodes

Info

C00033/1

AIN1: Output value

C00033/2

AIN2: Output value

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00034 | AINx: Configuration

Data type: UNSIGNED_8

Index: 24541

d

= 5FDD

h

Configuration of the analog inputs for current or voltage measurement

Analog terminals

Selection list

Info

0 -10V..+10V

Input signal is the voltage signal -10 V ... +10 V

• -10 V ... +10 V ≡ -100 % ... +100 %

1 0mA..20mA

Input signal is the current signal 0 mA ... 20 mA

• 0 mA ... 20 mA ≡ 0 % ... +100 %

2 4mA..20mA

Input signal is the current signal 4 mA ... 20 mA

• 4 mA ... 20 mA ≡ 0 % ... +100 %

• The current loop is monitored for open circuit

(I < 4 mA) by the device.

Subcodes

Lenze setting

Info

C00034/1

0: -10V..+10V

AIN1: Config.

C00034/2

0: -10V..+10V

AIN2: Config.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1