Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

887

15

Parameter reference

15.2

Parameter list | C00435

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00435

C00436

C00437

Parameter | Name:

C00435 | OxU/I: Offset

Data type: INTEGER_16

Index: 24140

d

= 5E4C

h

Offset of the analog outputs

Analog terminals

Setting range

(min. value | unit | max. value)

-199.99

%

199.99

Subcodes

Lenze setting

Info

C00435/1

0.00 %

O1U: Offset

C00435/2

0.00 %

O2U: Offset

C00435/3

0.00 %

O1I: Offset

C00435/4

0.00 %

O2I: Offset

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00436 | OxU: Voltage

Data type: INTEGER_16

Index: 24139

d

= 5E4B

h

Display of the voltage at the analog outputs

Analog terminals

Display range

(min. value | unit | max. value)

0.00

V

10.00

Subcodes

Info

C00436/1

O1U: Voltage

C00436/2

O2U: Voltage

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00437 | OxI: Current

Data type: INTEGER_32

Index: 24138

d

= 5E4A

h

Display of the current at the analog outputs

Analog terminals

Display range

(min. value | unit | max. value)

0.000

mA

20.000

Subcodes

Info

C00437/1

O1I: Current

C00437/2

O2I: Current

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000