Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

295

5

Motor control (MCTRL)

5.14

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.14.1

Device overload monitoring (Ixt)

C00064/1...3

displays the device utilisation (ixt) in [%] in different time intervals:

• If the device utilisation reaches the switch-off threshold set in

C00123

:

• The error response set in

C00604

will be carried out (Lenze setting: "Warning").

• The "

oC5: Ixt overload

" error message will be entered into the Logbook.

• The bMctrlIxtOverload status output of the

LS_DeviceMonitor

system block will be set to

TRUE.

• A setting of

C00604

= "0: No Reaction" deactivates the monitoring.

Parameter

Info

C00064/1

Device utilisation (Ixt)

• Maximum value of pulse utilisation (

C00064/2

)

and permanent utilisation (

C00064/3

).

C00064/2

Device utilisation (Ixt) 15s

• Pulse utilisation over the last 15 seconds (only for loads >160 %).

C00064/3

Device utilisation (Ixt) 3 min

• Permanent utilisation over the last 3 minutes.

Highlighted in grey = display parameter