Parameter reference

15.2

Parameter list | C00010

806

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00010

C00011

C00012

Parameter | Name:

C00010 | AIN1: Characteristic

Data type: INTEGER_16

Index: 24565

d

= 5FF5

h

From version 04.00.00

Analog terminals

:

Signal adaptation via characteristic

Setting range

(min. value | unit | max. value)

0.00

%

199.99

Subcodes

Lenze setting

Info

C00010/1

0.00 %

AIN1: (+y0) = min

C00010/2

0.00 %

AIN1: (+x0) = Dead band

C00010/3

0.00 %

AIN1: (-y0) = (-min)

C00010/4

0.00 %

AIN1: (-x0) = (-Dead band)

C00010/5

100.00 %

AIN1: (+ymax)

C00010/6

100.00 %

AIN1: (+xmax)

C00010/7

100.00 %

AIN1: (-ymax)

C00010/8

100.00 %

AIN1: (-xmax)

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00011 | Appl.: Reference speed

Data type: UNSIGNED_16

Index: 24564

d

= 5FF4

h

Setting the reference speed

• In the controller, all speed-related signals are processed to one reference variable in percent.

• Set a reference speed here that corresponds to 100 %.

• The frequency that corresponds to the set reference speed is displayed in

C00059

.

Note:

This is not a maximum limitation!

All values in percent in the controller may be in a range of 0 ... 199.99 %.
Setting range

(min. value | unit | max. value)

Lenze setting

50

rpm

60000 1500 rpm

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00012 | Accel. time - main setpoint

Data type: UNSIGNED_32

Index: 24563

d

= 5FF3

h

The

L_NSet_1

FB: Acceleration time of the ramp generator for the main speed setpoint

• Generally, this ramp generator is used for all speed-controlled technology applications.

Setting range

(min. value | unit | max. value)

Lenze setting

0.000

s

999.999 2.000 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000