6i/o terminals – Lenze 8400 HighLine User Manual

Page 330

Advertising
background image

6

I/O terminals

6.1

Digital input terminals

330

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Internal interfaces to the application

• Relevant inputs at the

LS_DigitalInput

system block:

• Relevant outputs at the

LS_DigitalInput

system block:

Identifier

DIS code | data type

Information/possible settings

Counting input DI1
bCountIn1_ResetCompare

BOOL

Reset status signal "Comparison value reached"

FALSETRUE The output bCountIn1_Compare is reset to FALSE.

bCountIn1_LoadStartValue

BOOL

Load starting value into counter

FALSETRUE The starting value set in

C02840/1

is accepted as the current count

value.

Counting input DI6
bCountIn6_ResetCompare

BOOL

Reset status signal "Comparison value reached"

FALSETRUE The output bCountIn6_Compare is reset to FALSE.

bCountIn6_LoadStartValue

BOOL

Load starting value into counter

FALSETRUE The starting value set in

C02840/3

is accepted as the current count

value.

Identifier

DIS code | data type

Value/meaning

Counting input DI1
bCountIn1_Compare

BOOL

Status signal "Comparison value reached"

FALSE Current count value < comparison value (

C02840/2

)

TRUE Current count value ≥ comparison value (

C02840/2

)

wCountIn1_HW

wCountIn1_LW

C02841/1

| WORD

Current count value

• Output as High and Low word (without sign)

• Possible counting range: 0 ... 2

31

- 1

Counting input DI6
bCountIn6_Compare

BOOL

Status signal "Comparison value reached"

FALSE Current count value < comparison value (

C02840/4

)

TRUE Current count value ≥ comparison value (

C02840/4

)

wCountIn6_HW

wCountIn6_LW

C02841/2

| WORD

Current count value

• Output as High and Low word (without sign)

• Possible counting range: 0 ... 2

31

- 1