3 parameterising the controller as can master, Parameterising the controller as can master, 11 system bus "can on board – Lenze 8400 HighLine User Manual

Page 701

Advertising
background image

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

701

11

System bus "CAN on board"

11.7

Communication phases/network management

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11.7.3

Parameterising the controller as CAN master

If the initialisation of the system bus and the associated status change from "Pre-Operational" to

"Operational" is not effected by a superimposed host system, the controller can instead be defined

to be a "quasi" master to execute this task.
The controller is configured as CAN master in

C00352

.

• Being the CAN master, the controller sets all nodes connected to the bus (broadcast telegram)

to the "Operational" communication status with the "Start remote node" NMT telegram. Only

in this communication status, data can be exchanged via process data objects.

• A delay time can be set in

C00356/1

which must expire after mains switching before the

controller transmits the "Start remote node" NMT telegram.

Tip!
Master functionality is only required during the initialisation phase of the drive system.

Parameter

Info

Lenze setting

Value Unit

C00352

CAN slave/master

Slave

C00356/1

CAN delay boot-up - Operational

3000 ms

Note!

The changes of the master/slave operation in

C00352

will not be activated until

• another mains switching of the controller

or

• the "Reset node" or "Reset communication" NMT telegram has been transmitted to

the controller.

The "CAN reset node" device command (

C00002/26

) is provided as an alternative to the

"Reset node" NMT telegram for the reinitialisation of the CAN-specific device

parameters.