2 setting the baud rate, 3 setting the node address, Setting the baud rate – Lenze 8400 HighLine User Manual

Page 692: Setting the node address, 11 system bus "can on board

Advertising
background image

11

System bus "CAN on board"

11.2

Possible settings via DIP switch

692

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11.2.2

Setting the baud rate

The baud rate can be set via code

C00351

or with the DIP switches a to d.

11.2.3

Setting the node address

The node address can be set via code

C00350

or with the DIP switches 1 to 64.

• The labelling on the housing corresponds to the values of the individual DIP switches for

determining the node address.

• The valid address range depends on the number of SDO channels set in

C00366

:

• 1 SDO (Lenze setting): 1 ... 127
• 2 SDO: 1 ... 63

Note!

• All DIP switches (a ... d, 1 ... 64) = OFF (Lenze setting):

• At switching on, the settings under code

C00350

(node address) and

C00351

(baud

rate) will become active.

• Preset baud rate: 500 kbps

DIP switch position

Baud rate

d

c

b

a

OFF

ON

OFF

ON

20 kbps

OFF

OFF

ON

ON

50 kbps

OFF

OFF

ON

OFF

125 kbps

OFF

OFF

OFF

ON

250 kbps

OFF

OFF

OFF

OFF

500 kbps

OFF

ON

OFF

OFF

1000 kbps*

* From version 11.00.00

Note!

• The addresses of the nodes must differ from each other.
• All DIP switches (a ... d, 1 ... 64) = OFF (Lenze setting):

• At switching on, the settings under code

C00350

(node address) and

C00351

(baud

rate) will become active.