Xx.0125.00001, Xx.0125.00002, Xx.0127.00002 – Lenze 8400 HighLine User Manual

Page 656: Xx.0127.00015, 9diagnostics & error management

Advertising
background image

9

Diagnostics & error management

9.9

Error messages of the operating system

656

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Sd15: Open circuit TL 4-fold [xx.0123.00207]

An01: AIN1_I < 4 mA [xx.0125.00001]

An02: AIN2_I < 4 mA [xx.0125.00002]

CE04: MCI communication error [xx.0127.00002]

CE0F: MCI control word [xx.0127.00015]

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Response (Lenze setting printed in bold)

Setting:

C00598/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Open-circuit monitoring for analog input 1 has tripped.

• Only if the analog input has been configured as a

current loop of 4 ... 20 mA (

C00034/1

= 2).

• Check wiring of the analog X3/A1I input terminal for

open circuit.

• Check minimum current values of the signal sources.

Response (Lenze setting printed in bold)

Setting:

C00598/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Open-circuit monitoring for analog input 2 has tripped.

• Only if the analog input has been configured as a

current loop of 4 ... 20 mA (

C00034/2

= 2).

• Check wiring of the analog X3/A2I input terminal for

open circuit.

• Check minimum current values of the signal sources.

Response (Lenze setting printed in bold)

Setting:

C01501/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Communication error with extension module in slot 1.

• Eliminate EMC interference.

• Switch off controller, correctly plug in the module,

switch on the controller again.

• Mains switching or restart of the controller,

respectively.

• Replace module/controller.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

Setting:

C00594/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Bit 14 ("SetFail") of the wMciCtrl control word of the

LS_DriveInterface

system block has been set.

Trace back signal source on the bus (e.g. PROFIBUS) that

sets bit 14 ("SetFail").