C00579 | resp. to max. speed/output freq. reached, C00580 | resp. to operating system error, C00581 | resp. to ls_seterror_x – Lenze 8400 HighLine User Manual

Page 918: C00579, C00580/1, C00581/1, C00581/2, C00581/3, C00581/4, C00581/5

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00579

918

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00579

C00580

C00581

Parameter | Name:

C00579 | Resp. to max. speed/output freq. reached

Data type: UNSIGNED_8

Index: 23996

d

= 5DBC

h

Response when the max. speed limit (

C00909

) or output frequency limit (

C00910

) has been reached.

Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
5 Warning

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00580 | Resp. to operating system error

Data type: UNSIGNED_8

Index: 23995

d

= 5DBB

h

From version 11.00.00

Response if the required computing time of the application exceeds the available computing time.
Selection list

0 No Reaction
1 Fault
5 Warning

Subcodes

Lenze setting

Info

C00580/1

0: No Reaction

Resp. to runtime exceedance

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00581 | Resp. to LS_SetError_x

Data type: UNSIGNED_8

Index: 23994

d

= 5DBA

h

Selection of the error responses for application error messages

• An application error message is tripped by a FALSE/TRUE edge at the binary inputs bSetError1...4.

Selection list

0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information

Subcodes

Lenze setting

Info

C00581/1

0: No Reaction

LS_SetError_1

: Resp. to bSetError1

C00581/2

0: No Reaction

LS_SetError_1

: Resp. to bSetError2

C00581/3

0: No Reaction

LS_SetError_1

: Resp. to bSetError3

C00581/4

0: No Reaction

LS_SetError_1

: Resp. to bSetError4

C00581/5

0: No Reaction

LS_SetError_2

: Resp. to bSetError1

C00581/6

0: No Reaction

LS_SetError_2

: Resp. to bSetError2

C00581/7

0: No Reaction

LS_SetError_2

: Resp. to bSetError3

C00581/8

0: No Reaction

LS_SetError_2

: Resp. to bSetError4

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1