17.1.102.1 Procedure of the mains failure control

A failure of the voltage supply of the power section can be detected by

• an evaluation of the DC-bus voltage

and/or

• an external monitoring system (e.g. voltage measuring relay).

The type of mains failure control to be used depends on the used drive system.

Evaluation of the DC-bus voltage
This proceeding is used for single drives or multi-axis drives which do not use an external

monitoring system.

• For evaluating the DC-bus voltage, you can use a comparator (e.g. FB

L_Compare_3

) as shown

in the following interconnection example 1.

• In order that the mains failure control will be activated if the DC-bus voltage falls below a

certain operating threshold, set the comparison function "2: In1 > In2" has to be set for the

FB

L_Compare_3

in

C00690

.

• For specifying the operating threshold, the SB

LS_ParFree_a_2

is used. This system block can

output 16 parameterisable analog signals. In the shown example, the operating threshold

has to be set in the "free parameter"

C00476/1

.

[17-43] Interconnection example 1: Evaluation of the DC-bus voltage with a comparator (cutout)

Use of an external monitoring system
In this proceeding, the digital status signal of an external monitoring system is connected to the

FB L_MFail_1 via a digital input of the controller.

• In the following example, the digital input DI7 is used.

• The active level (HIGH or LOW active) for DI7 has to be parameterised in

C00114

in such a way

that bFault becomes TRUE when the monitoring system is tripped.

• A free input of the application block can be used to transfer the digital input signal from I/O

level to application level.

[17-44] Interconnection example 2: Use of the digital status signal of an external monitoring system

Note!

The following interconnection examples are not functional yet. For an error-free

function, connect the FB L_MFail_1 with further signals!

IO level:

Application level: