17.1.102.5 Commissioning the mains failure control

Commissioning should be executed with motors without load.

1. Start the drive.
2. Set the acceleration time:

• Set the speed setpoint to 100 %, operate the controller with max. speed.
• Set controller inhibit and measure deceleration time up to standstill.
• Set approx. 1/10 of the measured deceleration time in

C01470/2

.

3. Set retrigger time:

• In case of mains failure control via detection of the DC-bus voltage level:

Set the deceleration time measured under point 2 in

C01470/3

.

• In case of mains failure control via an external system:

Set the time in which the drive is to be continued to be brought to a standstill under control

at short-term mains recovery in

C01470/3

.

4. Switch off the supply voltage (mains or DC bus).

The following profile is to be shown on the oscilloscope:

[17-47] Schematic diagram with activated mains failure control (ideal profile)

Stop!

The voltage setpoint must be below the operating threshold of a braking unit if

connected. If a connected braking unit responds, the drive with max. possible torque

(I

max

) will be braked. The desired operational performance gets lost.

n = speed of the drive

Operating threshold OU

Switch-on threshold - braking unit

Operating threshold - mains failure

Operating threshold LU

n

t

0

t

UG

0

0

1

nDcSet_a

2

L_Compare_3.bOut

3

t1

t2

Point in time Info

t = t1

Mains failure

t = t2

Speed "0" reached.