5

Motor control (MCTRL)

5.14

Monitoring

304

Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Note!

With automatic brake control:
In case of automatic brake control, the brake will only be released if no motor phase

failure exists and the magnetisation of the field-oriented control types is completed.
With manual brake control:
In case of manual brake control and forced release of the brake, the brake will be

controlled directly as before.
The user himself must ensure that the brake will only be opened if all of the following

conditions are met:

• Motor phase failure monitoring (

C00597

) and motor phase error monitoring before

operation (

C2866/2

) are active.

• The controller is enabled (controller enable).
• The bMctrlMotorPhaseFault status output of the SB

LS_DeviceMonitor

is set to FALSE.

• Bit 10 of the MCTRL_Status3 status word must be set to 0 before the brake opening is

triggered.

• When the controller is enabled, this bit is set to 1 and will not be set to 0 again

before the "Motor phase error monitoring before operation" is successfully

completed.

• The MCTRL_Status3 status word can be integrated in the application via

configuration parameters (e.g.

C00620

) (MCTRL_Status3 = selection 34906 in

Selection list - analog signals

).