Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

633

9

Diagnostics & error management

9.6

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.6.2

Setting the error response

When a monitoring function responds, the response set for this monitoring function (TroubleQSP,

Warning, Fault, etc.) will be triggered.

• For many monitoring functions the response can be individually parameterised via parameters.

Tip!
The table in the chapter "

Short overview (A-Z)

" contains the error messages for which the

response can be set.

( 644)

Warning thresholds
Some of the monitoring functions are activated if a defined warning threshold (e.g. temperature)

has been exceeded.

• The corresponding preset threshold values can be changed via the following parameters:

Parameter

Info

C00120

Setting of motor overload (I²xt)

C00123

Device utilisat. threshold (Ixt)

C00572

Brake resistor overload threshold

C00599

Motor phase failure threshold