Lenze · 8400 HighLine · Referenzhandbuch · DMS 10.0 EN · 06/2014 · TD05/TD14

233

5

Motor control (MCTRL)

5.9

Servo control (SC)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Motor current limitation
A cross current setpoint is calculated from the torque setpoint which is limited depending on the

magnetising current, the max. current in motor mode (

C00022

) and the max. current in generator

mode (

C00023

). The total current injected into the motor does not exceed the max. currents in

motor mode and in generator mode.

Note!

To avoid instabilities during operation, the torque limit values are internally processed

as absolute values.

Note!

For synchronous motors, the Lenze setting of the torque limits nTorqueMotLimit_a and

nTorqueGenLimit_a to 100 % can result in the activation of the torque limitation for

motor temperature < max. motor temperature before the set current limit values

(

C00022

,

C00023

) are reached.

• With a motor temperature of approx. 20°C and maximum load, the maximum current

will then be set to approx. 15 % below the set current limit values.

• Remedy: If the torque limits nTorqueMotLimit_a and nTorqueGenLimit_a are

increased to 115 %, the set current limit values can also be reached for a motor

temperature of 20°C and maximum load.