08.96

12 Functional Descriptions

12.33.2 Optimization of speed controller

12.33.2.1

Machine data

MD 1001:

Speed controller clock cycle

MD 1004:

Configuration control structure

MD 1406:

Speed controller type

MD 1407:

P gain speed controller

MD 1408:

P gain upper adaptation speed

MD 1409:

Reset time speed controller

MD 1410:

Reset time upper adaptation speed

MD 1411:

Lower adaptation speed

MD 1412:

Upper adaptation speed

MD 1413:

Select adaptation speed controller

MD 1414:

Natural frequency reference model speed

MD 1415:

Damping reference model speed

MD 1416:

Symmetrizing reference model speed

MD 1421:

Time constant integrator feedback

MD 1665:

Long-time factor IPO/NCONT cycle for ramp generator

12.33.2.2

Optimization of proportional gain of speed controller

The proportional gain is optimized as the first step in optimizing the speed controller. For this
purpose, MD 1409: Reset time speed controller is set to 500 ms, effectively deactivating the
integral-action component. The proportional component is then incremented until resonance
points in the system are reached (motor begins to whistle). The P gain which is determined by
this method must then be multiplied by a factor of 0.5. The product is then the start value for
the first frequency response measurement.

12.33.2.3

Optimization of integral-action component (reset time) of
speed controller

After the proportional gain has been determined, the reset time of the speed controller is
decreased until the amplitude response begins to rise above the 0 dB line. An increase over
the line of 3 dB is generally permitted. A value of < 20 ms is the target guide value for the
reset time.