12 Functional Descriptions

12.93

12.12.1 Execution of the function "Path dimension from the PLC"

Manual traverse commands (traverse keys) are ignored while the path dimension is being
traversed from the PLC.

If G68 is passed down the command channel, the path dimension on a rotary axis is traversed
along the shortest path (< 180°). The function G68 precludes the functions G90/G91. The
function G68 is active only for axes to which the partial function ”modulo programming” has
been assigned.

12.12.2

Termination of the function

Path dimension from the PLC

The path dimension function is terminated when an acknowledgement has been sent to the
PLC (command channel).

Positive acknowledgement (normal mode)
The function ”Path dimension from the PLC” is acknowledged positively when the
remaining path still to be traversed has reached the ”Exact stop window coarse” (MD
204). The acknowledgement frees the channel again, i.e. program mode can be continued
or restarted. If the channel is in the RESET state and if the path dimension is started, then
an NC start cannot be executed. The channel returns to the RESET state once the path
dimension is terminated. The path dimension cannot be started when a part program is
running (see negative acknowledgement).

Negative acknowledgement (error condition)
If an error occurs during path dimension processing, then the function is acknowledged
through specification of an error number (DB 41, DWm + 1).

12.12.3

Interruption

The path dimension function is interrupted when the following conditions are fulfilled:

Reset by key

RESET by a PLC user program

Change in operating mode

EMERGENCY STOP

Warm start

Cancellation of controller enable command

Follow-up mode

Parking axis

Traverse beyond the software or hardware limit switch or the working area limitation.

Note

All alarms which disable NC processing or mode group readiness to operate likewise terminate
the path dimension function. There are no additional alarms specific to the path dimension
function. If the function is aborted, then it is merely acknowledged negatively through
specification of an error number in DB41, DWm + 1. The function is also terminated when the
operating mode is changed without initiation of a reset.

When the following conditions are fulfilled, the active path dimension can be stopped; traversal
can however be continued until the desired position is reached:

Feed override 0 %

Axis-specific feed inhibit (PLC interface signal)

NC stop and feed stop do not have any effect on an active path dimension function.

12–96

© Siemens AG 1992 All Rights Reserved 6FC5197- AA50

SINUMERIK 840C (IA)