12.93

7 Drive Machine Data (SIMODRIVE Drive MD)

7.1.2 MSD MD (data description - SW 3)

Speed at start of field weakening motor 2

233

Default value

Lower input limit

Upper input limit

Units

Depends on motor

100

6 000

rev/min

Active on

Power On

Input of speed at which field weakening starts as specified on the motor data sheet (non-
Siemens motor) or automatic parameterization using machine data "Motor code number" (MD
238). In the field-weakening range, the magnetizing reactance X

h

increases linearly from the

saturated value at the speed at which field weakening begins to the unsaturated value at the
upper limit speed of the X

h

characteristic (see diagram MD 175).

Motor maximum speed motor 2

234

Default value

Lower input limit

Upper input limit

Units

Depends on motor

0

20 000

rev/min

Active on

Power On

Input of motor maximum speed as specified on the motor data sheet (non-Siemens motor) or
automatic parameterization using machine data "Motor code number" (MD 238).

Gain factor X

h

-characteristic motor 2

235

Default value

Lower input limit

Upper input limit

Units

Depends on motor

100

300

%

Active on

Power On

Input of gain factor (X

h2

/X

h1

) of the X

h

characteristic (magnetizing reactance) as specified on

the motor data sheet (non-Siemens motor) or automatic parameterization using machine data
"Motor code number" (MD 238). In the field-weakening range, the magnetizing reactance X

h

increases linearly from the saturated value at the speed at which field weakening begins to the
unsaturated value at the upper limit speed of the X

h

characteristic (see diagram MD 175).

Note:

If the value is unknown, then 100 % must be entered in order to obtain constant magnetizing
reactance over the entire speed range.

Breakdown torque reduction factor motor 2

236

Default value

Lower input limit

Upper input limit

Units

100

1

150

%

Active

at once

Input of breakdown torque reduction factor as specified on the motor data sheet. The point at
which the breakdown torque limit is applied can be altered in this machine data.

Settings of higher than 100 % increase the point at which the limit is applied and vice versa
with settings of lower than 100 %.

©

Siemens AG 1992 All Rights Reserved 6FC5197- AA50

7–33

SINUMERIK 840C (IA)