12.93

7 Drive Machine Data (SIMODRIVE Drive MD)

7.2.2 FDD MD (data description - SW 3)

f

PBM

in Hz

T

PBM

in

µ

s

2666.6....

375.0*

2782.6....

359.375

2909.0....

343.75

3047.6....

328.125

3200

312.5*

3368.4....

296.875

3555.5....

281.25

3764.7....

265.625

4000

250.0*

4266.6....

234.375

4571.4....

218.75

4923.0....

203.125

5333.3....

187.5*

5818.1....

171.875

6400

156.25

7111.1....

140.625

8000

125*

Note:

The pulse frequency can be specified only in the quantization given in the table above. Other
frequency inputs are rounded up or down to the next closest table value, e.g. 3150 Hz to
3200 Hz.

Calc. dead time current closed-loop

1101

Default value

Lower input limit

Upper input limit

Units

50

0

124

µ

s

Active on

Power On

The calculation dead time is the time which elapses between the start of a current control
clock cycle (input of current setpoint) and the activation of the control voltage setpoints on the
gating unit ASIC. The standard default value is automatically loaded during initial start-up when
machine data M1102 is input. In order to make the setpoints on all power sections "valid"
simultaneously (to achieve uniform dynamic response), the time required to calculate the most
complex axis (double axis) is entered.

Setting values (worstcase), execution times:

40

µ

s = single-axis module

50

µ

s = double-axis module

Note:

Limits of calculation dead time (violation leads to error message)

MD 1101 <

MD 1000 x 31.25

µ

s (=current controller clock cycle)

1

MD 1101 <

––––––––––––

4 x MD 1100

T

PBM

=

–––––

4

_______

*

A preselection with synchronous sampling period (TPWM) with respect to the controller cycles can be made

via the toggle button.

©

Siemens AG 1992 All Rights Reserved 6FC5197- AA50

7–49

SINUMERIK 840C (IA)