7 Drive Machine Data (SIMODRIVE Drive MD)

09.95

7.2.2 FDD MD (data description - SW 3)

Timer motor temperature alarm

1603

Default value

Lower input limit

Upper input limit

Units

240

0

600

s

Active

at once

Input of timer for the motor temperature alarm. When the value set in "Motor temperature
warning" (MD 1602) is exceeded, a message is transferred to the SERVO and a time monitor
activated. If the timer runs out before the temperature drops below the limit, the drive initiates
a generator braking operation and suppresses the transistor drive signals for the appropriate
axis after MD 1404 (pulse suppression) in conjunction with MD 1403 (creep speed).

Note:

Changing the timer setting will not influence a time monitoring function already in progress
(counter started). The change will become applicable when the motor temperature has
dropped below the warning limit (MD 1601).

ZK undervoltage warning threshold

1604

Default value

Lower input limit

Upper input limit

Units

200

0

600

V

Active

at once

Input of DC-link undervoltage warning threshold. When the voltage drops below this value, a
message is sent to the SERVO. This message is output on the 1st page of the FDD service
display: DC link "off".

Timer speed controller at fixed stop

1605

Default value

Lower input limit

Upper input limit

Units

200

20

10 000

ms

Active

at once

Input of "Speed controller at fixed stop" timer. The output of the speed controller (current
setpoint value) is monitored. In the event of a fault, the control pulses for the power section
transistors are suppressed on the drive side when the timer setting has expired.

Note:

Setting values of MD 1065 < MD 1404 (Timer pulse suppression) are rejected as parameteri-
zation errors.

The monitoring function is independent of internal operating modes (feedforward control,
function generator, etc.).

Status of binary inputs

1700

Default value

Lower output limit

Upper output limit

Units

0000

0000

7FFF

Hex

Active

at once

This machine data is used to display the status of the binary inputs.

7–70

©

Siemens AG 1992 All Rights Reserved 6FC5197- AA50

SINUMERIK 840C (IA)