07.97

6 NC Machine Data (NC MD), NC Setting Data (NC SD)

6.2 General machine data (general data)

When allocating the numbers, make sure that there is no collision with other M functions.
Generally, the following values are permissible:

0, 1, 2, 3, 4, 5, 17, 19, 30, 37

Example

MD 260 = 123

MD 261 = 456

M1 = 123 LF

Selection of C axis operation for spindle 1

M3 = 456 LF

Deselection of C axis operation for spindle 3

Note:

After C axis mode has been selected, all axes involved in the functions G02, G03, G12, G13,
G33, G34, G35, G36 must first have been traversed with G90.

Example

N10

M70

(Selection of C axis operation)

N20

G0 C0 Z5

(Traverse axes involved in thread cutting operation)

N30

G36 C0 Z-15 K3 F200

(Thread cutting position-controlled axes)

TO allowance for protection zone adjustment

300

Lower input limit

Upper input limit

Units

0

0

9999 9999

IS

Active on

Power On

Note:

For further information see description of the function collision monitoring.

Output byte to user interface

1)

310

Lower input limit

Upper input limit

Units

0

0

91, 92, 93 and 94

999 (as from SW 4)

-

Active on

Power On

Output byte to MIXED I/O

311

Lower input limit

Upper input limit

Units

0

0

11, 12, or 21, 22

999 (as from SW 4)

-

Active on

Power On

With NC MD 310 and 311, the cam signals can be assigned to an output byte of a certain HW
MIXED I/O. Enter either 11 or 91 if using the 1st output byte of the 1st MIXED I/O. Entering 22
or 92 gives an analog assignment of the output byte to the 2nd byte of the 2nd MIXED I/O.
The decimal values for the synchronous interface to the PLC are entered in the same way.
Both MDs have a default setting of 0. If illegal values are entered, alarm 45 is triggered.

Assignment of MIXED I/O module for emergency retraction

to a mode group

2)

312 - 317

Default value

Lower input limit

Upper input limit

Units

0

0

22, 94 (as from SW 4)

Active on

Power On

A signal can be output via a MIXED I/O group to trigger a fast emergency retraction if a fault is
caused by external HW. One output byte is used for each mode group.

_______

1)

As from SW 3

2)

MD 314 to MD 317 as from SW 4

©

Siemens AG 1992 All Rights Reserved 6FC5197- AA50