08.96

12 Functional Descriptions

12.33.5 Speed setpoint filter

Speed setpoint filter combinations

Filter 2

Filter 1

MD 1501

PT1

PT1

300

PT1

PT2

200

PT1

BS

201

PT2

PT1

100

PT2

PT2

000

PT2

BS

001

BS

PT1

102

BS

PT2

002

BS

BS

003

12.33.5.2

Bandstops and low passes as speed setpoint filter

Bandstop

Depending on requirements, the "Bandstop" function can be set in three configurations:

Simple bandstop. MD 1514/MD 1517 and MD 1515/MD 1518.

Bandstop with adjustable damping of amplitude response plus MD 1516/MD 1519.

Bandstop with adjustable damping of amplitude response and increase/decrease in
amplitude response above blocking frequency plus MD 1520/MD 1519.

Note

The sampling frequency of the control (MD 1001) sets an upper limit to the blocking frequency
input (parameterization error).

1

1

MD 1514 <

=

2 x T

sampl

2 x MD 1001

MD 1001 = T

sampl

=

62.5 µs

125.0 µs

MD 1514 <

8000 Hz
4000 Hz

Low pass

In the case of rigid mechanical components, the k

v

(servo gain) factor and dynamic response

of the subordinate speed control loop (incl. filter time constants and position controller
deadtimes) are indirectly proportional for the purpose of optimizing the position control loop.

If the k

v

(servo gain) factor setting is limited to lower values due to elastic mechanical

components (table frequencies), it is possible to use the filter time constant (as a component
of the subordinate dynamic response) as an additional degree of freedom to the servo gain
factor to dampen resonance without impairing the dynamic response of the position controller.

© Siemens AG 1992 All Rights Reserved 6FC5197- AA50

12–349

SINUMERIK 840C (IA)