7 Drive Machine Data (SIMODRIVE Drive MD)

7.3.2 Drive MD (data description)

Notes:

Setting the reset time to zero deactivates the I-action component for the range which is
greater than the machine data "Adaptation upper speed threshold (MD 1412) (see also
Note in MD 1409).

MD 1410 is not active when the "Speed controller adaptation" is deactivated
(MD 1413 = 0).

Caution:

When the adaptation function is active, deactivation of the I-action component for only one
speed range (MD 1409 = 0 and MD 1410 0 or vice versa) should be avoided (to prevent
problem of torque step changes through resetting of the integral value on transition from
adaptation to constant range).

Lower adaptation speed

1411

Default value

Lower input value

Upper input value

Units

0.0

0.0

50 000.0

rev/min

Active

at once

Input of lower speed threshold for adaptation of the speed controller machine data or automatic
parameterization (initialization) via operation ”Calculate controller data” for MSD. When the
adaptation function is active, the control machine data MD 1407 and MD 1409 are applied at
speeds n < MD 1411. In the adaptation range MD 1411 < n < MD 1412, linear interpolation
takes place between the two control machine data sets.

Graphic representation:

Adaptation of speed controller machine data by means of characteristic

n

MD 1411

K

P

, T

N

MD 1412

MD 1401

MD 1409

MD 1408

MD 1410

MD 1407

Lower speed

range with

constant P gain/

integral-action

time

Upper speed

range with

constant P gain/

integral-action

time

Adaptation
range

T

N

K

P

Upper adaptation speed

1412

Default value

Lower input value

Upper input value

Units

0.0

0.0

50 000.0

rev/min

Active

at once

Input of upper speed threshold for adaptation of the speed controller machine data or
automatic parameterization (initialization) via operation ”Calculate controller data” for MSD.
When the adaptation function is active, the control machine data MD 1408 and MD 1410 are
applied at speeds n > MD 1412. In the medium range MD 1411 < n < MD 1412, linear
interpolation takes place between the two control machine data sets. See machine data
"Adaptation lower speed threshold" (MD 1411) for diagram.

©