09.95

7 Drive Machine Data (SIMODRIVE Drive MD)

7.3.2 Drive MD (data description)

Damping speed setpoint filter 1

1507

Default value

Lower input limit

Upper input limit

Units

0.7

0.2

5.0

Active

at once

Input of damping for current setpoint filter 1 (PT2 low-pass). The filter is activated via machine
data MD 1200 (No. current setpoint filters) and MD 1201 (Type current setpoint filter).

Note:

With interpolating axes, the speed setpoint filter must always be parameterized
immediately.

Natural frequency speed setpoint filter 2

1508

Default value

Lower input limit

Upper input limit

Units

2 000.0

10.0

8 000.0

Hz

Active

at once

Input of natural frequency for speed setpoint filter 2 (PT2 low-pass). An entry of < 10 Hz as
the natural frequency of the low-pass filter initializes the filter as a proportional element with a
gain of 1 independently of the associated damping. The filter is activated via machine data
MD 1500 (No. speed setpoint filters) and MD 1501 (Type speed setpoint filter).

Note:

With interpolating axes, the speed setpoint filter must always be parameterized immediately.

Damping speed setpoint filter 2

1509

Default value

Lower input limit

Upper input limit

Units

0.7

0.2

5.0

Active

at once

Input of damping for speed setpoint filter 2 (PT2 low-pass). The filter is activated via machine
data MD 1500 (No. speed setpoint filters) and MD 1501 (Type speed setpoint filter).

©

Siemens AG 1992 All Rights Reserved 6FC5197- AA50

7–127

SINUMERIK 840C (IA)