Siemens SINUMERIK 840C User Manual

Page 357

Advertising
background image

6 NC Machine Data (NC MD), NC Setting Data (NC SD)

09.95

6.7 Axis-specific MD 2 (axial data 2)

Measuring time 1 (neural QEC only) (as from SW 4)

1372*

Default value

Lower input limit

Upper input limit

Units

600

1

9999 9999

% of MD 1236*

Active on
NC Stop

Measuring time 2 (neural QEC only) (as from SW 4)

1376*

Default value

Lower input limit

Upper input limit

Units

300

1

9999 9999

% of MD 1236*

Active on
NC Stop

Measuring time 3 (neural QEC only) (as from SW 4)

1380*

Default value

Lower input limit

Upper input limit

Units

300

1

9999 9999

% of MD 1236*

Active on
NC Stop

Measuring times MD 1372* - 1380* are used to set the adaptation of the measuring duration to
determine the fault criteria during the neural quadrant error compensation learning phase (MD
1812*, bit 0 and 1).

If this measuring duration is to remain constant, all 3 machine data must be parameterized to
the same value. Reparameterization of the standard value is usually not necessary because a
percentage is entered in MD 1236*.

The middle measuring duration (MD 1376*) is also used for conventional quadrant error
compensation if the service QEC display is used to make the settings.

Special features:

If the value 0 is entered in MD 1236*, 100% = 10 ms, as otherwise it is not possible to
parameterize error measuring times > 0.

Torque compensation controller P component

(as from SW 4.4)

1384*

Default value

Lower input limit

Upper input limit

Units

100

0

1 000 000

0.0001%

Active on
NC Stop

The P gain of the torque compensation controller is parameterized in % of the ratio drive
maximum speed to nominal torque of the slave drive. The input variable of the torque
compensation controller is the difference in torque between master and slave, the output
variable is a speed setpoint. See also MD 1812* and 523*.

Formula:

Output variable = P gain * control difference

Example:

A torque difference of 10 % of the slave nominal torque and standard parameterization 100
(= 0.01%) produces an output variable of the controller of 0.001 % of the maximum speed of
the slave drive (0.01 % * 10 % = 0.001 %).

6–172

©

Siemens AG 1992 All Rights Reserved 6FC5197- AA50

SINUMERIK 840C (IA)

Advertising
This manual is related to the following products: