7 Drive Machine Data (SIMODRIVE Drive MD)

12.93

7.2.2 FDD MD (data description - SW 3)

Monitoring cycle

1002

Default value

Lower input limit

Upper input limit

Units

100 000

4 000

100 000

µ

s

Active on

Power On

The interrupt clock cycle is used for high-priority monitoring purposes. Note: The input value
for the clock cycle must be a whole multiple of 4 ms (parameterization error).

m x 4000

µ

s

m=1, 2, 3, ..., 25

Note:

The interrupt level must not be exceeded otherwise the drive will be tripped.

No. encoder marks motor measuring system

1005

Default value

Lower input limit

Upper input limit

Units

2 048

128

8 192

Incr/rev

Active on

Power On

Input of number of encoder increments per motor revolution of the motor measuring system.

Note:

The indirect measuring system must always be configured for FDD/MSD.

Frequency pulse-width modulation

1100

Default value

Lower input limit

Upper input limit

Units

3 200

2 000

8 000

Hz

Active on

Power On

The frequency of the sampling triangle in the PWM inverter is defined in this machine data.
The frequency values are set as an MMC function (see attached table).

Value table:

f

PBM

in Hz

T

PBM

in

µ

s

2000

500.0*

2064.5....

484.375

2133.3....

468.75

2206.8....

453.125

2285.7....

437.5*

2370.3....

421.875

2461.5....

406.25

2560

390.625

_______

*

A preselection with synchronous sampling period (TPWM) with respect to the controller cycles can be made

via the toggle button.

7–48

©

Siemens AG 1992 All Rights Reserved 6FC5197- AA50

SINUMERIK 840C (IA)