7 Drive Machine Data (SIMODRIVE Drive MD)

09.95

7.2.2 FDD MD (data description - SW 3)

P-gain current controller

1120

Default value

Lower input limit

Upper input limit

Units

0

0

10 000

V/A

Active

at once

Input of proportional gain of current controller or automatic parameterization using machine
data "Motor code number" (MD 1102). It defines the relationship between control voltage
setpoint and control deviation current.

Integral-action time current controller

1121

Default value

Lower input limit

Upper input limit

Units

0

0

10 000

µ

s

Active

at once

Input of control quantity "Integral-action time of current controller" or automatic
parameterization using machine data "Motor code number" (MD 1102).

Note:

Integral arm can be disabled by entering the value T

N

= 0.

Selection current setpoint filter

1200

Default value

Lower input limit

Upper input limit

Units

1

0

4

Active

at once

Input of number of current setpoint filters. Band-stop and low-pass filters are available; these
are set via the machine data "Configuration current setpoint filter" (MD 1201).

Selection of number of filters:

0

No current setpoint filter activated

1

Filter 1 activated

2

Filters 1 and 2 activated

3

Filters 1, 2 and 3 activated

4

Filters 1, 2, 3 and 4 activated

Note:

Before a filter is activated, the filter type and the appropriate filter machine data must be input.

7–56

©

Siemens AG 1992 All Rights Reserved 6FC5197- AA50