6 NC Machine Data (NC MD), NC Setting Data (NC SD)

04.96

6.7 Axis-specific MD 2 (axial data 2)

Filter time constant acceleration determination for quadrant

error compensation (as from SW 4)

1256*

Default value

Lower input limit

Upper input limit

Units

60

0

16 000

1 ms

Active on

NC Stop

This value is usually not altered by the user. The value should only be increased if the
compensation in the smallest speed range is insufficient.

Feedfwd control factor for rigid tapping (as from SW 2)

1260*

Default value

Lower input limit

Upper input limit

Units

0

0

1 000

0.1 %

Active on

NC Stop

A P feedforward control factor can be entered for the axes involved in the function ”Rigid
tapping”. This machine data has the same meaning as that of NC MD 312*. NC MD 1260* is
only used if NC MD 1320* is not 0.

Grid spacing / ENDAT measuring step (as from SW 5.4)

1264*

Default value

Lower input limit

Upper input limit

Units

0

0

16 000

-

Active on

Power On

The SINUMERIK 840C supports ENDAT absolute encoders where the ratio of grating
pitch/ENDAT measuring step as an integer can be divided by 4. If you enter an incorrect value,
this leads to measuring errors. The input values 0 to 7 are internally processed as the value 4
(default value for rot. EQN 1325). The grid spacing and the ENDAT measuring step must be
taken from the data sheet of the ENDAT absolute encoder.

Setpoint filter time constant

1272*

Default value

Lower input limit

Upper input limit

Units

0

0

1 000

0.1 ms

Active on

NC Stop

The setpoint filter prevents overshooting of positions in the case of a dynamic speed
feedforward control of 100 %.

Note:

As from SW 4, for 8 parameter blocks

Setpoint
filter

Setpoint

+

Setpoint

speed

Actual position value

K

V

Feedforward factor

Symmetrizing
filter

d
dt

6–166

©

Siemens AG 1992 All Rights Reserved 6FC5197- AA50

SINUMERIK 840C (IA)