7 Drive Machine Data (SIMODRIVE Drive MD)

10.94

7.1.2 MSD MD (data description - SW 3)

Maximum motor temperature motor 1

63

Default value

Lower input limit

Upper input limit

Units

Depends on motor

0

170

°C

Active

at once

Input of maximum motor temperature. The value entered can be lower than the maximum
temperature value calculated via the motor code number (MD 96) and motor data set. If the
specified temperature is exceeded, the "Motor overtemperature" prewarning is output after
approximately 30 s (provided it is activated) or the "Motor overtemperature" alarm given after
the delay set in machine data MD 65.

Fixed temperature

64

Default value

Lower input limit

Upper input limit

Units

0

0

170

°C

Active

at once

Input of fixed temperature. If a value higher than 0 is entered, then the motor is operated at the
specified fixed temperature value.

Note:

The motor temperature monitoring function set in machine data MD 63 is made inoperative if a
fixed temperature is specified.

Timer motor temperature alarm

65

Default value

Lower input limit

Upper input limit

Units

240

0

600

s

Active

at once

Input of timer for the motor temperature alarm. A warning is output as soon as the monitor
responds; the drive is then tripped with an alarm message when the delay time set above has
expired.

Address DAC2

72

Default value

Lower input limit

Upper input limit

Units

3048

0000

FFFF

Hex

Active

at once

Note:

This machine data is not included in the machine data lists. The DACs are configured in the
course of the drive servo start-up procedure for diagnostic purposes.

Input of memory address of which the contents must be output.

3048 H: Motor utilization M

d

/M

dmax

or P/P

max

7–10

©

Siemens AG 1992 All Rights Reserved 6FC5197- AA50

SINUMERIK 840C (IA)