7 Drive Machine Data (SIMODRIVE Drive MD)

09.95

7.3.2 Drive MD (data description)

Note:

Before the filter type is configured, the appropriate filter machine data must be input.

Time constant speed setpoint filter 1

1502

Default value

Lower input limit

Upper input limit

Units

0.0

0.0

500.0

ms

Active

at once

Input of time constant for speed setpoint filter 1 (PT1 low-pass). The filter is deactivated when
the data is set to zero.

Time constant speed setpoint filter 2

1503

Default value

Lower input limit

Upper input limit

Units

0.0

0.0

500.0

ms

Active

at once

Input of time constant for speed setpoint filter 2 (PT1 low-pass). The filter is deactivated when
the data is set to zero.

Natural frequency speed setpoint filter 1

1506

Default value

Lower input limit

Upper input limit

Units

2 000.0

10.0

8 000.0

Hz

Active

at once

Input of natural frequency for speed setpoint filter 1 (PT2 low-pass). An entry of < 10 Hz as
the natural frequency of the low-pass filter initializes the filter as a proportional element with a
gain of 1 independently of the associated damping. The filter is activated via machine data MD
1500 (No. speed setpoint filters) and MD 1501 (Type speed setpoint filter).

Note:

With interpolating axes, the speed setpoint filter must always be parameterized immediately.