10.94

7 Drive Machine Data (SIMODRIVE Drive MD)

7.1.2 MSD MD (data description - SW 3)

With a setting of, for example, 100 %, the rated torque acts as the torque limit up to rated
speed. At speeds above the rated value, the torque limit curve drops in proportion to 1/n so
that the rated output is reached in each case. MD 270 - MD 273, MD 47 and MD 290 are the
corresponding machine data.

Generative limitation motor 2

270

Default value

Lower input limit

Upper input limit

Units

100

5

100

%

Active

at once

Input of torque limit for braking operation (generator-mode torque limit). This input value is
referred to the maximum motor-mode torque (see also MD 269).

2nd torque limiting value motor 2

271

Default value

Lower input limit

Upper input limit

Units

50

5

100

%

Active

at once

Input of 2nd torque limit value referred to the 1st torque limit (MD 269). This 2nd torque limit
can be selected via the PLC control word and machine data MD 290.

Switchover speed for MD 270 motor 2

272

Default value

Lower input limit

Upper input limit

Units

500

0

Maximum motor

speed

rev/min

Active

at once

Input of speed above which the generator-mode limit set in machine data MD 270 is applied
(see also MD 269).

Hysteresis MD 272 motor 2

273

Default value

Lower input limit

Upper input limit

Units

20

0

Maximum motor

speed

rev/min

Active

at once

Input of hysteresis for the switchover speed set in machine data MD 272 (see also MD 269).

Cut-in speed torque setpoint smoothing motor 2

274

Default value

Lower input limit

Upper input limit

Units

4 000

0

Maximum motor

speed

rev/min

Active

at once

Input of speed value above which the torque setpoint smoothing function activated in machine
data MD 44 is applied.

©

Siemens AG 1992 All Rights Reserved 6FC5197- AA50

7–41

SINUMERIK 840C (IA)