17

Parameter reference

17.2

Parameter list | C00569

1010

Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00569

C00570

Parameter | Name:

C00569 | Resp. to peak current

Data type: UNSIGNED_8

Index: 24006

d

= 5DC6

h

Configuration of monitoring of the motor control (group 1)
Selection list

0 No Reaction
1 Fault
5 Warning

Subcodes

Lenze setting

Info

C00569/1

0: No Reaction

Response for overcurrent detection and clamp operation

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00570 | Resp. to controller limitations

Data type: UNSIGNED_8

Index: 24005

d

= 5DC5

h

Configuration of monitoring of the motor control (group 2)
Selection list

0 No Reaction
1 Fault
5 Warning

Subcodes

Lenze setting

Info

C00570/1

0: No Reaction

Response if direct-axis current controller is limited

• e.g. at servo control (

SC

)

C00570/2

0: No Reaction

Response if cross current controller is limited

• e.g. at servo control (

SC

)

C00570/3

0: No Reaction

Response if torque setpoint is limited

• Limitation of the speed controller output, the

differential setpoint precontrol, and of the additive

torque at (

SC

) servo control and (

SLVC

) sensorless

vector control.

C00570/4

0: No Reaction

Response if field controller is limited

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1