1221

17

Parameter reference

17.2

Parameter list | C01446

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C01446

C01447

C01448

Parameter | Name:

C01446 | L_Sequencer_1: ZählerVergleichswert

Data type: INTEGER_32

Index: 23129

d

= 5A59

h

From version 12.00.00

L_Sequencer_1: "Counting" action

Setting range

(min. value | unit | max. value)

-2147483647

2147483647

Subcodes

Lenze setting

Info

C01446/1

0

L_Sequencer_1

: Count. act. 1: comparison value

C01446/...

...

C01446/8

L_Sequencer_1

: Count. act. 8: comparison value

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01447 | L_Sequencer_1: ZählerSprungziel

Data type: UNSIGNED_16

Index: 23128

d

= 5A58

h

From version 12.00.00

L_Sequencer_1: "Counting" action

Setting range

(min. value | unit | max. value)

0

100

Subcodes

Lenze setting

Info

C01447/1

0

L_Sequencer_1

: Count. act. 1: Jump destination

C01447/...

...

C01447/8

L_Sequencer_1

: Count. act. 8: Jump destination

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01448 | L_Sequencer_1: ZählerVergleichsfunktion

Data type: UNSIGNED_16

Index: 23127

d

= 5A57

h

From version 12.00.00

L_Sequencer_1: "Counting" action

Selection list

1 Counter content = comparison value
2 Counter content > comparison value
3 Counter content >= comparison

value

4 Counter content < comparison value
5 Counter content <= comparison

value

Subcodes

Lenze setting

Info

C01448/1

1: Counter content = comparison

value

L_Sequencer_1

: Count. act. 1: Comparison op.

C01448/...

...

C01448/8

L_Sequencer_1

: Count. act. 8: Comaprison op.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Advertising